Technical Data:
Parameters(25°C) Model | SCK11- | |||
50A | 100A | 200A | 300A | |
Nominal Rms Current (Ipn) | ±50AT | ±100AT | ±200AT | ±600AT |
Measuring Range (Ip) | 150AT | 300AT | 600AT | 750AT |
Load resistance Rmax | ≥10kΩ | |||
Output Voltage | ±4V or ±5V | |||
Working voltage | DC ±12V or ±15V(±5%) | |||
Accuracy @ Ta=25°C | ±1% FS | |||
Linearity @ Ta=25°C | ±1% FS | |||
Withstand voltage | 2.5kVrms/50Hz/min | |||
Offset Voltage | < ±30mV | < ±15mV | ||
Offset temperature characteristics | < ±0.08%/°C | < ±0.05%/°C | ||
Thermal drift of Vo | < ±2mV/°C | < ±1mV/°C (If=0) | ||
Hysteresis offset | < ±30mV | < ±20mV (if=F.S. 0<-->Nominal RMS Current) | ||
Response time | < 5μs | |||
Current consumption | <±15mA | |||
Operating temperature | -20~+80 °C | |||
Storage temperature | -40~+85 °C |
Instructions
1. Size error: ±1mm;
2. Primary aperture: φ20mm;
3. Fastening hole: φ4.5mm*2;
4. Output terminal: 2EDGIV-5.08-4P;
Mating plug: 2EDGIK-5.08-4P;
5. The IP indication direction is the positive direction of the current;
6. The temperature of the primary conductor shall not exceed 105°C;